[HCL] GE Critical Power - VH Series UL - supported by snmp-ups (mib = ietf) #2429
Comments
Thanks a lot for this report, more so with the twist of running on Windows. Did you build your own, or use the tarballs auto-made by NUT recipes on AppVeyor CI? Got any hints to share for others who would endeavour with the revived NUT for Windows effort - e.g. how did you register the service(s) so an OS shutdown is actually handled? Did any of the known-incomplete bits (quite a long list can be seen in the project) bite you in practice of this use-case? Also, I'd expect the default IiRC the message itself is about trying a query for SysOID (in the IETF namespace) for a redirection to vendor-defined data (if any), and that OID was not served. |
I am using the executables from the AppVeyor CI generated 7z artifact (https://ci.appveyor.com/project/nut-travis/nut/history) and wrote a PowerShell script to register I was not hindered by any of the known-incomplete bits, but the information on running it on Windows is quite scattered around. Also, there are a few things that changed between the old 2.6.5 Windows release and now. For example I needed to run the command shell as admin in order to be able to create the When using the default About the OID, see http://oid-info.com/cgi-bin/display?oid=1.3.6.1.4.1.818.1.1&a=display and chapter "4 SNMP AGENT" of the SNMP Card manual https://library.industrialsolutions.abb.com/publibrary/checkout/GE_UPS_OPM_CNT_SNM_BAS_CRD_1GB_V022?TNR=Software%7CGE_UPS_OPM_CNT_SNM_BAS_CRD_1GB_V022%7CPDF&filename=GE_UPS_OPM_CNT_SNM_BAS_CRD_1GB_V022.pdf#page=38. I can try to get a SnmpWalk output next week. |
Thanks for the insights! Probably, a practical chapter in the Wiki (or a new page) would be useful - thanks in advance :) As for service registration, allegedly the
No comments at the moment about pipe creation - not sure if it really requires privileges or something else was at play... I can only guess that the driver running as a Windows service would be sufficiently privileged. Otherwise, the Windows-side code of NUT did not change very much as part of the revival from 2.6.5-based branch. Was your earlier easier experience with same version/instance of Windows itself - maybe it is the OS that changed in some important aspect? Regarding OpenSSL libraries - were there any particular complaints? I see that the In fact, did the Finally, re-checked the note about file sizes, and agree that they seem excessive. At the moment (per |
I am using NUT 2.8.2 on Windows with the following UPS: GE Critical Power, Model VH2000 UL
When I have
mibs = auto
inups.conf
I receive the following message when running.\nut.exe -N
In the HCL list, there are two devices listed under "GE Digital Energy".
"GE Digital Energy" "ups" "2" "EP Series" "USB" "blazer_usb"
"GE Digital Energy" "ups" "2" "GT Series 1000/1500/2000/3000 VA Rack/Tower" "UL-version" "blazer_ser"
GE Digital Energy was rebranded to GE Critical Power and then later acquired by ABB
https://electrification.us.abb.com/products/uninterruptible-power-supplies-ups/vh-series-ups-ul-listed-700va-3kva-previous-generation
General information about the UPS
GE VH Series UPS: https://library.industrialsolutions.abb.com/publibrary/checkout/GEA-D1057?TNR=Brochures%7CGEA-D1057%7CPDF&filename=VCL-UL-VH-UL-brochure-GEA-D1057-GB-y15m12d09-mr.pdf
Technical Data Sheet: https://library.industrialsolutions.abb.com/publibrary/checkout/OPM_VHU0K73K0XU?TNR=Installation%20and%20Instruction%7COPM_VHU0K73K0XU%7CPDF&filename=GE_UPS_OPM_VHU_0K7_3K0_XUS_V011.pdf
SNMP Card: https://library.industrialsolutions.abb.com/publibrary/checkout/GE_UPS_OPM_CNT_SNM_BAS_CRD_1GB_V022?TNR=Software%7CGE_UPS_OPM_CNT_SNM_BAS_CRD_1GB_V022%7CPDF&filename=GE_UPS_OPM_CNT_SNM_BAS_CRD_1GB_V022.pdf
MIB file: https://www.circitor.fr/Mibs/Mib/G/GESINGLEUPS-MIB.mib
I have successfully tested a shutdown sequence with the UPS.
upsc
output withmibs = ietf
upscmd
output withmibs = ietf
upsrw
output withmibs = ietf